Skip to content
/ motor Public

synApps module: motor (for git testing purposes only - not for production use)

Notifications You must be signed in to change notification settings

tboegi/motor

Repository files navigation

motor

Build Status

This is a fork of https://github.com/epics-modules/motor/

Changes to upstream motor, the most important ones

v7.2.3-ESS, based on R7-3-1, see release notes from there

Bug fixes

ff7ad73fc:motorRecord.html: Document bit 6 and 7 of .MFLG field

Improvements

2dc310171: (and some more commits) Add MINP for soft motors

2e89b5527: (and some more from upstream) ...add raw softlimts RLLM, RHLM needed when MRES changes

v7.0.9-ESS, based on R7-2-2

Bug fixes

2420d29d2: motorRecord: Reset JOGR/JOGF when LLS/HLS is active

f3f8b3b27: motorRecord.cc: doBackLash may hung up when on LS

Improvements

40537595b: Add MOTOR_FLAGS_NO_TWEAK_ON_LS

738314c57: asynMotorController: Do not move, when power on fails

1c6e4884: motorRecord.cc: Suppress LVIO if not homed

v7.0.8-ESS, based on R7-2-2 + latest master

Bug fixes

3358621ef: motorRecord: Do not do a retry when RA_PROBLEM is set

41183c9c8: motorRecord.cc: Do not move if VAL - RBV == RDBD

524696a8d: Fix negative backlash with relative moves in a negative direction

f149e8d7a: motorRecord: retry-relative follows motor/master (mostly)

c90d6a780: motorRecord.cc: Fix for SPMG=Pause and CALLBACK_DATA

24ef7b207: motorRecord.cc: Fixes for NTM

Improvements

4c7949067: motorRecord: Do not home when both limit switches are active

bd7e007e8: asynMotorAxis.cpp: Distinguish PowerOff vs PowerOff Auto

47bbd9354: motorRecord: loosen the close enough calculation

7d181592d: asynMotorController.cpp: make autoPowerOn() more rebust

6cc882fc3: motorRecord.cc/motorDevSup.h: Use CARD as axis number in printing

700d424f4: motorRecord: fall back to ACCS if JAR is 0.0

073ae178e: MotorRecord: Add NTM UPDATE

v7.0.7-ESS, based on R7-2-2

Bug fixes

50d99515e: motorRecord: Correct printing of special(DBF_MENU)

240d12c9d: motorRecord.cc: Fix for SPMG=Pause and CALLBACK_DATA

fc8d9e956: motorRecord.cc: Fixes for NTM

1f5666358: mototRecord.cc: Fixes for NTM

1557ee7f6: motorRecord.cc: If controller uses EGU, keep VELO when UREV changes

Improvements

8cb38dbba: Remove non-up-to-date motor_release-ESS.html

982ef46ee: MotorRecord: Add NTM UPDATE

d1a597ffa: motorRecord.cc: More debug logs around SPMG

8efb77707: motorRecord.dbd: .SPMG is special SPC_MOD

v7.0.6-ESS, based on R7-2-2

Bug fixes

fb6027cbb: asynMotorController.cpp: NULL pointer check for pasynUserController_

b47408f37: motorRecord.cc: Do not move further on limit switch

ab535ead6: motorRecord/maybeRetry(): Do not retry if limit swicth is active

41c2bc5cc: Fix NTM=1 RTRY=1 bug: Motor stopped, but never moved

fc1bda9c0: motordrvCom.h needs shareLib.h

Improvements

8bfdd9d50: motorRecord.cc: More printing in doDVALchangedOrNOTdoneMoving()

6c7833aac: motorRecord.cc: More printing around last VAL

ef91f0a0f: motorRecord.cc: More printing around commandedDval

v7.0.5-ESS

Bug fixes

8e1047d1: motorRecord: JOGF=1 and writing to e.g. LLM stopped

380b35b0: asynMotorAxis.cpp: Only update motorStatus_ if needed

0bb7c2a3: devMotorAsyn.c: Handle MF_DRIVER_USES_EGU in position restore

e0db111f: motorRecord.cc: Fix printing in special() for links

173355c5: Add shareLib.h

Improvements

c7b58b60: Save-Restore: Add restore_needed

1ac030da: devMotorAsyn.c: Introduce priv.saveRestore

4e67cc7a: asynMotorController::readGenericPointer: Improve asynError

c4eb8bc0: asynMotorAxis.cpp: Add positionWritten

afa150b6: devMotorAsyn.c: Rename pasynUserSync into pasynUserSyncFloat64

c3d59ab8: Merge 'github/asynMotor-remove-initEvent' into ess-master

c966d921: Add devPositionRestoreNeeded() and use it

49da10eb: motorRecord.cc: Improve prints about neverPolled

6b982fe0: Make flags in MFLG field more usable

855f0678: motorRecord.cc: Sanitize ERES after MRES

1764b559: motorRecord.cc: Add one more debug in init_re_init()

74e65c7d: devMotorAsyn.c: Add debug print around RSTM

debba9e2: asynMotorController.cpp: autopwerOff and no jog

5bea53be: asynMotorController.cpp: Handle status in writeInt32()

6c7ef0cb: motorRecord.cc: Remove printing of RA_DIRECTION

166d19ae: motorRecord.cc: Reduce spam printing of RA_DIRECTION

0e87222a: motorRecord.cc: Introduce mr_stops_on_ls_activated()

f213c1d5: motorRecord.cc: Less LS special handling with cdir

b81edb83: motorRecord.cc: Cleanup around clear_xx_buttons

90643807: devMotorAsyn: remove initEvent in init_record()

v7.0.4-ESS

Bug fixes

ca0747aa: Fixes around load_pos related to MRES

7a25fed5: devMotorAsyn.c: Initialize pmr->flags early

46dfadb1: motorRecord.cc: Correct handling of RRES

5d825112: motorRecord.cc: clear_buttons() when hitting a limit switch

44a1ad3a: motorRecord.cc: Reset JOGF/JOGR in motor-has-stopped

Improvements

ff79e4c5: motorRecord.cc: More printout levels; devSupGetInfo()

8d6e0da0: asynMotorController.cpp: Handle status of poll()

d8a43e9b: motorRecord.cc: Debug backlash and retry count

153b8616: motorRecord.cc: print value in special()

54f86b90: Improve printing of MIP

v7.0.3-ESS

Bug fixes

54c4286b: LOAD_POS: Ignore MRES when driver uses EGU

146f43ee: Improve handling of ramp-down after stop

146f43ee: Record recognizes motor stop while jogging

Improvements

19dc53c1: devMotorAsyn: Introduce Debug prints

v7.0.2-ESS

Update to the latest motor/master, 2020-08-06, Includes upstream R7-2-1

Bug fixes

7546277f: JVEL while jogging, MF_DRIVER_USES_EGU is used

c92efe25: Late connect: Don't mis-use UDF, use neverPolled

Improvements

RSTM field (Restore mode)

The RSTM field is in upstram master,
but today not part of an official release

b64af248: .SPAM field: Initialize it in motorRecord.dbd

The motorRecord state machine is sometimes hard to follow.
In order to make sure that we can follow all the transitions
(especially when the driver reports "DONE") there is a new logging
from inside the motorRecord itself.
A simplified version of a move triggered by writing to the .VAL field
of the PV "IOC:m1" looks like this:
2020/06/26 13:29:15.370 [motorRecord.cc:1833 IOC:m1] doRetryOrDone dval=158.9 rdbd=0.1
2020/06/26 13:29:15.370 [motorRecord.cc:1853 IOC:m1] mipSetBit 'Mo' old='' new='Mo'
2020/06/26 13:29:15.375 [motorRecord.cc:1462 IOC:m1] msta.Bits.RA_DONE=0
2020/06/26 13:29:15.487 [motorRecord.cc:1442 IOC:m1] msta.Bits.RA_MOVING=1
2020/06/26 13:29:18.119 [motorRecord.cc:1442 IOC:m1] msta.Bits.RA_MOVING=0
2020/06/26 13:29:18.119 [motorRecord.cc:1462 IOC:m1] msta.Bits.RA_DONE=1
2020/06/26 13:29:18.119 [motorRecord.cc:1574 IOC:m1] motor has stopped drbv=158.970
2020/06/26 13:29:18.119 [motorRecord.cc:1231 IOC:m1] maybeRetry: close enough; rdbd=0.1diff=-0.07 mip=0x20('Mo')
2020/06/26 13:29:18.119 [motorRecord.cc:1234 IOC:m1] mipClrBit '...' old='Mo' new=''

If you don't want these printouts, set the .SPAM field to produce less loggings

d7b19882: motorRecord.cc: Print the date and time in Debug()

v6.9.7-ESS

Updates from upstream, motor R7.0

3b3625b7c84 "Remove the config from controller code"

When most (configuration) values can be read from the controller,
this was possible to push those values into the motorRecord fields.
(For example the default velocity was copied into VELO)

Remove all this logic from the record and asyn device support.
If needed, the driver can set up ai records which can be forwarded
into the record fields with help of ao records.

The only parameters that are left are the "read only softlimits".
They are needed to restrict DHLM and DLLM inside the working range
of the axis.

db759583 "motorRecord.cc: Correct SPDB handling when MRES == 1.0"

ae5e1fae "Add a SPAM field"

Make the enable/disable of printouts more fine-grained,
now we use a bit mask in the new introduced SPAM field:

 1 STOP record stops motor, motor reports stopped
 2 MIP changes,  may be retry, doRetryOrDone, delayReq/Ack
 3 Record init, UDF changes, values from controller
 4 LVIO, recalcLVIO
 5 postProcess
 6 do_work()
 7 special()
 8 Process begin/end

36177f7b "motorRecord.cc: Add ACCS field"

The problem:
When a user changes the velocity by writing to the VELO field,
but forgets to write to the ACCL field, the acceleration will
change and may be too high.
(Note: Many users are not aware of this side-effect).

Solution:
Introduce a field called ACCS, "Acceleration in seconds^2".

Once the field is written, the ACCL field is updated and the
acceleration is "locked".
It is locked for changes of VELO.
It can be be unlocked by writing to ACCL.

If the acceleration is locked (or not) is stored in the field ACCU,
which can be either "motorACCSused_Accl" or "motorACCSused_Accs".

And in this sense ACCU is not a lock, but just keeps track which
of the accelation fields ACCL or ACCS has been updated last, and
should be used in the next movement.
In any case an update to ACCS updated ACCL and the other way around.
Thanks to Mark Rivers for this nice idea.

a01e46ef "Don't allow DHLM=DLLM=0 when read-only limits are set"

b912ecc7 "Move EGU"

Make it possible to forward movements (absolute/relative) from the
record into the model 3 driver:
- Add a new device support function, moveEGU
- Add it to the device suppport table for asyn motors, entry #9
- Use writeGenericPointer in asynMotorController to receive
  the new command.
- Add moveEGU() in asynMotorAxis, this function can be overloaded
  by a driver.
- Add moveVeloEGU() in asynMotorAxis, this function can be overloaded
  by a driver.

v6.9.6-ESS

Updates from upstream, motor R6.11

Beside many bugfixes and improvements, here some high lights:

8eacc2f0 "Adapt motorRecord.cc to base-3.16 with typed rset"

ee9fca1d "Fixes for problems that showed up in base 7.0. -

 It was using the value of mr->[link]->value.constantStr
 and mr->[link]->value.pv_link.pvname without checking the
 link types.   This was incorrect, and led to errors because
 constantStr no longer has a defined value if the link type
 is not CONSTANT.   Changed so that it only accesses these
 union fields if the link is the correct type.
 - It did not check if pv_link.pvname was NULL before calling
   CA functions, though now that we check the link type perhaps
   this cannot occur.
 - It did not lock the motor record before accessing the fields.
 - Added Debug calls to show the link types and values."

95c0a4ca "Don't set "stop" field true if driver returns RA_PROBLEM true.

 It is the driver's responsiblity to stop a motor if the condition
 that results in the RA_PROBLEM bit being set doesn't result
 in the motor automatically stopping."

7493d50b "If URIP=Yes and reading RDBL causes LINK error,

 do not start a new target position move."

8eacc2f0 "Adapt motorRecord.cc to base-3.16 with typed rset"

689a813a "Merge branch 'add_SPDB_v1'",

 Rename SDBD into SPDB

f3d3d2cb 'Add Adjust after homed'

When homing against a limit switch, we find the motor position
most often outside the valid soft limit range.
Make it possible to move the motor inside the allowed range,
by settting the "motorFlagsAdjAfterHomed_" parameter to 1.

9c2c0c6f "STOP when hitting a limit switch is configurable"

When a limit switch is hit when traveling into the commanded direction,
the motorRecord sends a STOP.
There are cases, when this is not desired:
- The IOC is running while the motion controller is commissioned.
  The  motor is moved using an engineering tool,
  The motorRecord does not have a valid "commanded direction".
  The motion controller will stop the motor, when a limit switch is
  hit, and this shouldbe tested manually.
- The motor is homed against a limit switch.
  The controller will stop the motor, and then move it slowly away from
  the switch.
  Once the switch releases, the current position is latched.

Note:
Different controllers and use cases may need different behaviour(s),
so more commits and changes may come in the future.

Late connect

Improve the situation when an IOC is started a long time before the
controller "goes online".
The basic idea is to keep the record in "UDF".
Different commits like
84d0d09b "devMotorAsyn: Keep record in longer in UDF if needed"

When the communication with an asyn motor has not be established when the
record is iniitialized, keep the record in UDF.
(The record processing can not wait here)

Controller uses EGU

Modern controller use engineering units, so that the IOC uses e.g.
"mm" instead of "steps" when communicating positions.
The motorRecord insists somewhat to use steps.
As a result, both MRES must be set to some value, and then
the controller must have a "scale factor", "stepsPerUnit" or the like.
Solution:
  setIntegerParam(pC_->motorFlagsDriverUsesEGU_,1);
Note that there is still a need to set either MRES or SPDB to a useful
value, otherwise the motorRecord will refuse to move distances below
1.0 mm.

Read-only soft limits from controller

The model 1 and model 2 drivers can refuse to accept soft-limits.
The soft limits in the motorRecord stay always inside the physical
driving range of the axis.
Example: The controller has a driving range 0..175 mm
The user tries to set the DHLM field to 180mm.
The device support in the driver is allowed to refuse the change,
so that the DHLM field stays ar 175.
Similar for DLLM, and the user coordinate-ish LLH and LLM
This has never been implemented for model 3 drivers.
If available, the "read only softlimits" can be written
into the parameter library like this:
  pAxis->setDoubleParam(motorHighLimitRO_, limitHigh);
  pAxis->setDoubleParam(motorLowLimitRO_,  limitLow);
And device support will forward them to the motorRecord.

Homing ignores limit switches

The motorRecord assumes that there is a "home switch",
which needs to be activated.
The user must know, where the motor is, and decide if she wants
to use HOMF or HOMR to initiate the homing.
This does not work well if
- (a) The limit switch itself is the "home switch"
- (b) The homing sequence is like this
      "go to the low limit switch, activate it, stop, reverse the
      direction and search for the home switch.
In case of (a) will the motorRecord send a stop to the controller,
which may abort the homeing and leaves the axis in an unusable state.
In case of (b) the same problem occurs.
Solution:
  setIntegerParam(pC_->motorFlagsNoStopOnLS_, 1);
There is another, sometime annoying, thing:
When we have a controller, that can do a homing even when a limit
switch is active, the motorRecord will ignore HOMF when HLS set.
It silently ignores HOMR when LLS is active.
So again, the user must choose between HOMR/HOMF.
Solution:
  setIntegerParam(pC_->motorFlagsHomeOnLs_, 1);

Enhanced auto-power-on

There are 2 improvements in the new "auto power on mode 2"
The old auto power on had 0 (=off) and 1 (=on).
The new mode "2" has two more features:
- setting a power off timout < 0.0 will leave the axis
  powered on.
- The fixed power on delay can be shortened, if the axis
  reports "power on achieved" earlier.
  A better documentation of this feature is needed.

All MRES related calculation are in motorDevSup.c

The code in the motorRecord was full of DVAL/RVAL calculations,
dividing by MRES was needed everywhere.
This version uses dial coordinates in the motorRecord.cc
and let motorDevSup.c convert them into "raw" values. 

Compiler warnings removed

Removed all compiler warnings in the motor module.
(Those that my compilers showed)

About

synApps module: motor (for git testing purposes only - not for production use)

Resources

Stars

Watchers

Forks

Packages