Skip to content

Demo integration Atmocube Air Quality monitor + Levoit Air Purifier

License

Notifications You must be signed in to change notification settings

atmotube/atmocube-levoit-demo

Repository files navigation

Atmocube integration demo

Demo integration Atmocube Air Quality monitor + Levoit Air Purifier

This demo demonstrates how to use Atmocube local interfaces and get the air quality data to control purifier via cloud API.

The following interfaces are demonstrated:

  • Modbus TCP
  • Modbus RTU
  • BLE

Modbus TCP + Levoit 200S demo

Make sure Modbus TCP is enabled via Atmocube configuration tool.

Installation (Python 3.10):

pip install pyvesync
pip install pymodbus

Create local_settings.py with the following parameters

ATMOCUBE_IP = '192.168.1.149' #set your real Atmocube IP here
ATMOCUBE_IP_PORT = 502
LEVOIT_EMAIL = '[email]' #set levoit account email
LEVOIT_PASSWORD = '[password]' #set levoit account password

Run script

python atmocube-modbus-tcp.py

Output should be the following:

Found device: Air Purifier
is_on = False
details = {'filter_life': 0, 'mode': 'manual', 'level': 0, 'display': False, 'child_lock': False, 'night_light': 'off'}
features = []
modes = ['sleep', 'off', 'manual']
---------------------
TVOC = 0.07 ppm
PM1 = 3.4 ug/m3
PM2.5 = 3.6 ug/m3
PM4 = 3.6 ug/m3
PM10 = 3.6 ug/m3
CO2 = 1233 ppm
t = 22.67 C
h = 72.08 %
abs_h = 14 g/m3
p = 1019.2 mbar
noise = 43 dBa
light = 240 Lux
co = 0.0 ppm
o3 = 0.0 ppm
ch2o = 0.0 ppm
Address (hex) Address (decimal) Name Units Format
0x40 64 Total Volatile Organic Compounds (TVOCs) ppb uint16_t
0x41 65 PM 1.0 µg/m3 x 10 uint16_t
0x42 66 PM 2.5 µg/m3 x 10 uint16_t
0x43 67 PM 4 µg/m3 x 10 uint16_t
0x44 68 PM 10 µg/m3 x 10 uint16_t
0x45 69 Carbon dioxide (CO2) ppm uint16_t
0x46 70 Temperature Celcius x 100 int16_t
0x47 71 Humidity % x 100 uint16_t
0x48 72 Absolute humidity g/m3 uint16_t
0x49 73 Pressure mbar x 10 uint16_t
0x4A 74 Noise dB uint16_t
0x4B 75 Light Lux uint16_t
0x4C 76 Nitrogen dioxide (NO2) ppb uint16_t
0x4D 77 Carbon monoxide (CO) ppb uint16_t
0x4E 78 Ozone (O3) ppb uint16_t
0x4F 79 Formaldehyde (CH2O) ppb uint16_t
0x50 80 Color temperature K uint16_t
0x51 81 People index (0 to 100) index uint16_t
0x52 82 VOC index index uint16_t
0x53 83 NOx index index uint16_t

Modbus RTU

Make sure Modbus RTU is enabled via Atmocube configuration tool.

Connect RS485<>USB cable to Atmocube. Check the serial port number. It should be COM[x] for Windows or /dev/[x] for Linux/MacOS.

RS-485 Atmocube
GND GND
TXD+ A
TXD- B

Atmocube RS-485 connection

Installation (Python 3.10):

pip install pymodbus

Create local_settings.py with the following parameters

ATMOCUBE_RTU_PORT = '/dev/cu.usbserial-AQ027VNZ' #set your serial port name here
ATMOCUBE_RTU_DEVICE_ID = 10 #modify id according to Atmocube configuration tool
ATMOCUBE_RTU_BAUDRATE = 115200
ATMOCUBE_RTU_DATA_BITS = 8
ATMOCUBE_RTU_PARITY = 'N'
ATMOCUBE_RTU_STOP_BITS = 1 

Run script

python atmocube-modbus-rtu.py

Output should be the following:

---------------------
TVOC = 0.07 ppm
PM1 = 2.7 ug/m3
PM2.5 = 3.6 ug/m3
PM4 = 4.2 ug/m3
PM10 = 4.5 ug/m3
CO2 = 1338 ppm
t = 22.24 C
h = 72.72 %
abs_h = 14 g/m3
p = 1018.0 mbar
noise = 39 dBa
light = 53 Lux
ch2o = 0.0 ppm
Address (hex) Address (decimal) Name Units Format
0x3F 63 Total Volatile Organic Compounds (TVOCs) ppb uint16_t
0x40 64 PM 1.0 µg/m3 x 10 uint16_t
0x41 65 PM 2.5 µg/m3 x 10 uint16_t
0x42 66 PM 4 µg/m3 x 10 uint16_t
0x43 67 PM 10 µg/m3 x 10 uint16_t
0x44 68 Carbon dioxide (CO2) ppm uint16_t
0x45 69 Temperature Celcius x 100 int16_t
0x46 70 Humidity % x 100 uint16_t
0x47 71 Absolute humidity g/m3 uint16_t
0x48 72 Pressure mbar x 10 uint16_t
0x49 73 Noise dB uint16_t
0x4A 74 Light Lux uint16_t
0x4B 75 Nitrogen dioxide (NO2) ppb uint16_t
0x4C 76 Carbon monoxide (CO) ppb uint16_t
0x4D 77 Ozone (O3) ppb uint16_t
0x4E 78 Formaldehyde (CH2O) ppb uint16_t
0x4F 79 Color temperature K uint16_t
0x50 80 People index (0 to 100) index uint16_t
0x51 81 VOC index index uint16_t
0x52 82 NOx index index uint16_t

BLE (Bluetooth advertising)

Installation (Python 3.10):

pip install bleak

On MacOS installation may be tricky. You have to modify Info.plist for terminal app. See Bleak troubleshooting.

Create local_settings.py with the following parameters

ATMOCUBE_BLE_NAME = 'CUBE_004C' #set your Atmocube device BLE name CUBE_[last 4 MAC address characters]

Run script

python atmocube-ble.py

Output should be the following:

---------------------
TVOC = 0.10 ppm
PM1 = 3.3 ug/m3
PM2.5 = 3.5 ug/m3
PM10 = 3.5 ug/m3
t = 22.68 C
h = 72.09 %
CO2 = 1328 ppm
p = 1019.3 mbar
noise = 43 dBa
light = 240 Lux
CH2O = 0.0 ppm
CO = 0.0 ppm
O3 = 0.0 ppm
FW = 1.10.1.29

About