Configuring Modbus sMAP driver

The device type specific configuration of the modbus sMAP driver takes place in a CSV file specified in the sMAP configuration file. (See the register_config argument of the volttron.drivers.modbus.Modbus in the sMAP config example [ControllerAccess].) An example file can be found in the voltron-list repository at volttron/drivers/example.csv

The CSV file should be comma delimited. An Excel spreadsheet converted to CSV should work fine, even with commas in the data.

The CSV file requires a header line with the following columns labeled in any order (without quotes):

"PNNL Point Name"

The name to used access the point. References to this point will use name.

"Units"

Used for meta data when creating point information on the sMAP historian.

"Modbus Register"

A string representing how to interpret the data register and how to read it it from the device. The string takes two forms:

  • "BOOL" for coils and discrete inputs.
  • A format string for the Python struct module. See http://docs.python.org/2/library/struct.html for full documentation. Note that sMAP only supports numerical types. Strings will not work. Also the supplied format string must only produce one value.
      • Examples:
      • ">f" - A big endian 32-bit floating point number.
      • "
      • ">l" - A big endian 32-bit integer.

"Writable"

Either TRUE or FALSE. Determines if the point can be written to. If TRUE an actuation point will be created in addition to the normal point representing periodically scraped data. Only points labeled TRUE can be accessed through the ActuatorAgent.

"Point Address"

Modbus address of the point. Cannot include any offset value, it must be the exact value of the address.

"Notes"

Additional notes for the point.

Example

Additional columns may be added at the user discretion as long as they are labeled differently.

The following is a simple example:

Point Name PNNL Point Name Units Units Details Modbus Register Writable Point Address Notes
SampleFloat SampleFloat PPM 0.00-2000.00 >f FALSE 1001 CO2 Reading 0.00-2000.0 ppm
SampleWritableFloat SampleWritableFloat PPM 1000.00 (default) >f TRUE 1003 Setpoint to enable demand control ventilation
SampleLong SampleLong Enumeration 1 through 13 >l FALSE 1005 Status indicator of service switch
SampleWritableShort SampleWritableShort % 0.00 to 100.00 (20 default) >H TRUE 1007 Minimum damper position during the standard mode
SampleBool SampleBool On / Off on/off BOOL FALSE 1101 Status indidcator of cooling stage 1
SampleWritableBool SampleWritableBool On / Off on/off BOOL TRUE 1102 Status indicator